Contemporary-control-systems BACnet Cube I/O BMT-AO4 Manual de usuario Pagina 3

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 3
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 2
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Germany
Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com
Continuation Software Description
Function Table for Analog Output
Out_Of_Service Priority_Array Present_Value Analog Output OUT_OF_SERVICE
0
NULL Relinquish_Default Relinquish_Default
0
Value Value Value
1
NULL Relinquish_Default
unchanged 1
Value Value
Analog Value Object 1
Property Remark / Value RW
Object_Identifier analog-value, instance 1 R
Object_Type ANALOG_VALUE (2) R
Object_Name max. 42 Bytes, default “Watchdog Time” RW-E
Description max. 84 Bytes, default “ RW-E
Present_Value
Time Constant of Watchdog Timer,
0: Watchdog is inactive, Maximum: 655.34 seconds
RW-E
Status_Flags
IN_ALARM: 0
FAULT: 0
OVERRIDDEN: 0
OUT_OF_SERVICE: 0
R
Event_State NORMAL (0) R
Out_Of_Service FALSE (0) R
Units seconds (73) R
R: Read Property, W: Write Property, -E: Storage in EEPROM / Flash
The Watchdog Timer resets Present_Value of all output objects to Relinquish_Default, if BACnet communication fails permanently. The timer is re-
started, when a BACnet message with an APDU is received.
When the timer times out, the priority arrays of all output objects are completely cleared to NULL.
Vista de pagina 2
1 2 3

Comentarios a estos manuales

Sin comentarios