TD071105-0IA
5
Cabling Considerations
When attaching signal cables to the EIDX, Table 1 should be considered.
100 Mbps
50/125 or 62.5/125 µm
2 km (6562 ft)
Half-Duplex :
100 Mbps
15 km (49213 ft)
Half-Duplex :
Table 1 — Cabling Considerations
Observe in Table 1 that segment distance is very limited when using copper
media — regardless of data rate. Although 10BASE-T links can successfully
use Category 3, 4 or 5 cable — 100BASE-TX segments must use Category 5.
A popular choice for improved distance is multimode fibre — which also gives
good electromagnetic noise immunity and optimum protection from lightning
strikes. Considerable distance can be achieved in full-duplex mode — and the
greatest distance can be realized in full-duplex mode with single-mode fibre.
Note that half-duplex operation yields a modest, fixed distance which does not
vary with the type of fibre in use. This is because half-duplex mode is limited
by the collision domain — irrespective of the length and type of fibre.
EIDX switches offer three types of field connectors. Copper ports accept RJ-45
modular plugs. Two choices of fibre connectors are available: ST and SC.