TD100700-0MB
33
5.2.1 Universal Input — Configured as Analog Input
(Channels UI1–UI8)
You can measure 0–10 V with UI1–UI8 as follows:
Access the Main Page (Figure 13) and click a title link from among UI1–UI8.
Under BAS Channel Configuration in the new page that appears, set the
Channel Type to Analog Input. An example appears in Figure 19.
Under BACnet Object Configuration, the Units value defaults to VOLTS.
Attach your device to the pair of BASC20 pins for the chosen channel — so
that the more positive connection is to pin A and the more negative to pin C.
Figure 19 — Universal Input Configured as Analog Input