20-point BACnet/IP Sedona Field Controller
INSTALLATION GUIDE
INTRODUCTION
The BAScontrol20 (BASC20) is a 20-point field controller with a direct
connection to an IP/Ethernet network. Ideally suited for structured wiring
systems, the BASC20 is BACnet/IP compliant with a B-ASC device
profile. Having a resident Sedona Virtual Machine (SVM), the unit is freely
programmable using tools such as Niagara Workbench or Sedona Workbench.
For remote Ethernet I/O applications, the unit can be configured with minimal
effort using a standard web browser.
The BASC20 provides a convenient mix of universal inputs, binary inputs and
outputs as well as analog outputs. Models exist for both triac and relay binary
outputs. The unit is ideal for unitary control or for expanding I/O points in the
field via an Ethernet connection:
Versatile Control Device remote I/O, router and controller
Direct connection to an IP/Ethernet network
Compliant with BACnet/IP and B-ASC device profile
Powered by Sedona Framework™ Controller
Configurable with a standard web browser
Real-Time clock with super-cap backup
Flexible Input/Output 20 points of I/O
Eight configurable universal inputs
Thermistor, analog voltage, binary input, pulse inputs (4 channels)
Four binary inputs
Four analog voltage outputs
Four relay or triac output models
The BASC20 provides the ultimate in flexibility. It can be used for expansion
I/O at remote locations where an Ethernet connection exists. It can operate as a
function block programmable controller with its resident Sedona Framework
Virtual Machine. The BASC20 can operate as remote I/O for BACnet/IP and as
a Sedona Framework controller at the same time. A 10/100 Mbps Ethernet port
allows connection to IP networks and popular building automation protocols
such as BACnet/IP, and Sedona SOX. Twenty points can be configured through
resident web pages. The unit provides eight universal I/O points and four binary
outputs plus an additional four binary inputs and four analog outputs.
BAScontrol20
Vista de pagina 0
1 2 3 4 5 6 ... 15 16

Indice de contenidos

Pagina 1 - BAScontrol20

20-point BACnet/IP Sedona Field Controller INSTALLATION GUIDE INTRODUCTION The BAScontrol20 (BASC20) is a 20-point field controller with a direct

Pagina 2 - Outputs (Points AO1 – AO4)

TD100700-0IA 10 Analog Outputs AO1–AO4 Voltage in the range of 0–10 VDC (with up to 4 mA of current) can be outputted. No configuration is necessa

Pagina 3 - IP Reset Button

TD100700-0IA 11 Binary Inputs BI1–BI4 To sense the action of a push-button or relay, the contacts must have no applied energy, and be rated for low

Pagina 4 - INSTALLATION

TD100700-0IA 12 Figure 12 — Steps for Changing the IP Address of the PC Used for Setup Webpage Configuration The BASC20 contains a web server — bro

Pagina 5

TD100700-0IA 13 NEED MORE HELP INSTALLING THIS PRODUCT? Additional information can be found in the technical documentation available on our web sit

Pagina 6

TD100700-0IA 14 [This page is intentionally blank.]

Pagina 7

TD100700-0IA 15 [This page is intentionally blank.]

Pagina 8

TD100700-0IA 16 [This page is intentionally blank.]

Pagina 9

TD100700-0IA 2 SPECIFICATIONS Universal Inputs (Points UI1 – UI8) (web page configurable) Analog inputs: 0–10 VDC or 0–20 mA (with external resi

Pagina 10

TD100700-0IA 3 Figure 1 — RJ-45 Jack Electrical (± 10%) (Intended for use with Class 2 circuits.) Input (DC or AC) DC AC Voltage (V, ±10%):

Pagina 11

TD100700-0IA 4 INSTALLATION The BASC20 is intended to be panel-mounted in an industrial enclosure or wiring closet with screws (not provided). See

Pagina 12

TD100700-0IA 5 Powering The unit requires a source of 24 VDC or VAC via a two-pin removable keyed connector. NOTE: This device is intended for use

Pagina 13 - DECLARATION OF CONFORMITY

TD100700-0IA 6 Field Connections When attaching devices, observe proper cabling using Figure 3 as a guide. Figure 3 — Sample Wiring Diagram Attach

Pagina 14 - TD100700-0IA

TD100700-0IA 7 Universal Input — Configured for Analog Input A Universal Input can measure voltage in the range of 0–10 VDC or current in the range

Pagina 15

TD100700-0IA 8 Universal Input — Configured for Binary Input To sense the action of a push-button or relay, the contacts must have no applied energ

Pagina 16

TD100700-0IA 9 Universal Input — Configured for Pulse Input Assuming a 50% duty cycle, a pulse rate up to 40 Hz can be measured on channels UI1–UI4

Comentarios a estos manuales