Contemporary-control-systems BASrouter Installation Guide (Firmware 2.x) Manual de usuario Pagina 19

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 24
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 18
TD071200-0IK
19
those passed by the router from BACnet/IP. The default value
usually provides good performance.
6.4.5 MS/TP Baud Rate (Default Value = 38400)
The baud rate of the MS/TP network can be 9600, 19200, 38400
or 76800 bps. All MS/TP devices on the same MS/TP network
must use the same baud rate. On power up, as the router polls
for other masters, autobauding devices adjust to its baud rate.
6.4.6 MS/TP Tolerance (Default Selection = Strict)
This setting determines the degree to which interoperability with
devices is successful. The Lenient option is less efficient for
traffic flow but optimises interoperability. A slight improvement
in performance will be realised by selecting the Strict setting.
Vista de pagina 18
1 2 ... 14 15 16 17 18 19 20 21 22 23 24

Comentarios a estos manuales

Sin comentarios